Seismic Attachments Fig. 1000
(631)665-9300

Fast Clamp Sway Brace Attachment

“Fast Clamp” Sway Brace Attachment – Fig. 1000

For more product information please call (631) 665-9300
Diagram Notes

Max. Horizontal Design Load (UL) – 1” (25mm) through 2” (50mm) pipe size 655 lbs. (2.91kN)

Material

Carbon Steel, also available in 304 and 316 stainless steel

Finish

Plain

Service

A restraint device intended for lateral bracing.

Approvals

Underwriters Laboratories Listed in the USA (UL) and Canada (cUL). Approved for use with Allied Dyna Flow sprinkler pipe up to 2” as restraint device. Maximum horizontal design load is 655 lbs. (2.91kN) Torque requirement is 6-8ft./lbs. (8-10Nm). Approved by the State of California Office of Statewide Health Planning and Development (OSHPG).

Ordering

Order first by pipe size to be braced, followed by pipe size used for bracing, figure number, and finish.

Notes

The cross reference number for this product is Fig 010

Click Here for cross reference page for this product.
distributedistributedistributedomestic
  • Pipe Size
    in (mm)
    1 (25)
    1-1/4 (32)
    1-1/2 (40)
    2 (50)
    2-1/2 (65)
    3 (80)
    3-1/2 (90)
    4 (100)
    5 (125)
    6 (150)
Approximate Weight/100
1” Brace Pipe
1-1/4” Brace Pipe
  • Lbs
    71.6
    74.8
    77.8
    84.1
    90.2
    97.3
    104.0
    110.3
    123.1
    136.5
  • (Kg)
    32.5
    33.9
    35.3
    38.1
    40.9
    44.1
    47.2
    50.0
    55.8
    61.9
  • Lbs
    75.8
    79.1
    82.1
    88.4
    94.6
    101.7
    108.4
    114.6
    127.4
    140.8
  • (Kg)
    34.4
    35.9
    37.2
    40.1
    42.9
    46.1
    49.2
    52.0
    57.8
    63.8
Max Horizontal Design Load (FM) *
30-44 degrees
45-59 degrees
60-74 degrees
75-90degrees
  • Lbs
    200
    200
    200
    200
    200
    230
    230
    230
    -
    -
  • kN
    0.89
    0.89
    0.89
    0.89
    0.89
    1.02
    1.02
    1.02
    -
    -
  • Lbs
    280
    280
    280
    280
    280
    320
    320
    320
    -
    -
  • kN
    1.24
    1.24
    1.24
    1.24
    1.24
    320
    320
    320
    -
    -
  • Lbs
    340
    340
    340
    340
    340
    400
    400
    400
    -
    -
  • kN
    1.51
    1.51
    1.51
    1.51
    1.51
    1.78
    1.78
    1.78
    -
    -
  • Lbs
    380
    380
    380
    380
    380
    450
    450
    450
    -
    -
  • kN
    1.69
    1.69
    1.69
    1.69
    1.69
    2.00
    2.00
    2.00
    -
    -
* Max Horizontal Design Load (FM) Notes

- Load rating for LW above refers to FM Approved Lightwall Pipe commonly referred to as “Schedule 7”. These ratings may also be applied with EN 10220 and GB/T 8163 steel pipe.

- Load rating for “Schedule 10” above may be applied to GB/T 3092, EN 10255M, and H, or JIS G3454, FM Approved Thinwall, or “Schedule 40” steel pipes.